In the Florida Building Code, a kitchen hood is one piece of a larger system made up of the hood, grease duct, exhaust fan and makeup air. All four are tested together before final approval. The building department and the fire marshal decide what they accept for a given building, and Commercial Kitchen 101 only passes requests on to local companies.
Two hood types
The Mechanical volume of the code sorts hoods into Type I and Type II.
- Type I covers cooking that gives off grease or smoke, such as fryers, griddles, charbroilers and ranges. When one is installed, the hood, duct, exhaust equipment and makeup air each follow the same set of code sections.
- Type II sits over dishwashers and other equipment that produces heat or moisture without grease or smoke.
The code carves out two exceptions to the Type I requirement: electric appliances that pass the UL 710B low-grease test, and listed solid-fuel pizza ovens vented directly.
A Type I hood bears a label with its minimum exhaust rate, in cubic feet per minute for each linear foot. Construction is steel of at least No. 18 gage or stainless of at least No. 20, with outside seams welded liquid-tight. Grease filters are listed to UL 1046.
Airflow by cooking duty
The required rate rises with the heaviness of the cooking and depends on whether the hood hangs on a wall or over an island. Figures are cfm per linear foot of hood:
| Cooking duty | Wall-mounted canopy | Single island canopy |
|---|---|---|
| Extra-heavy | 550 | 700 |
| Heavy | 400 | 600 |
| Medium | 300 | 500 |
| Light | 200 | 400 |
Where a single hood covers different appliances, the heaviest one sets the rate. The code assigns appliances to duty classes, and a mechanical engineer or hood supplier can say where each one lands.
A local company can take it from here. One form, free for restaurants.
Get connectedThe grease duct
This duct moves grease-laden air from the hood up to the roof. A fire inside it travels fast, which explains how strict the code is.
- Steel of at least No. 16 gage, or stainless of at least No. 18.
- Joints welded or brazed liquid-tight on the outside, checked with a light test using a lamp of at least 100 watts.
- Eighteen inches of clearance from combustible construction.
- Cleanouts no more than 20 feet apart and within 10 feet of any turn over 45 degrees. Access doors are steel and liquid-tight, and a sign reads "ACCESS PANEL. DO NOT OBSTRUCT."
- Enclosure wherever the duct crosses a ceiling, wall, floor or concealed space, rated at least one hour and matching the assembly it passes through. A grease duct holds no fire or smoke dampers.
- A roof discharge at least 40 inches above the roof surface, 10 feet from property lines and 10 feet above grade.
Cleaners get into the duct through those cleanouts. The hood cleaning guide covers inspection frequency and what follows a finding of grease.
Roof fans
A grease system uses "upblast" fans on the roof. The code wants them hinged and held by a flexible, weatherproof cable, with the duct rising at least 18 inches above the roof beneath the fan.
Makeup air and balance
What leaves through the hood has to be replaced. The code wants makeup air from every source to roughly equal the exhaust, and mechanical makeup air must start and run with the exhaust fan. Makeup air should differ from room temperature by no more than 10 degrees Fahrenheit, subject to an exception in the code. The design plans include an outdoor air balance schedule or diagram, and the installer can supply the schedule that matches them.
Suppression tied to the hood
An approved automatic suppression system is required for every appliance that needs a Type I hood. When the system discharges, it also cuts fuel or electric power to the cooking equipment. The fire suppression guide covers that system.
The performance test
Final approval calls for a performance test of the hood system. It measures exhaust airflow and makeup airflow and checks the design intent. Smoke or steam is used to confirm capture and containment.
A kitchen with a history
An older hood approval says little about its present state. A new tenant can ask for:
- The latest hood cleaning certificate and service report.
- The most recent six-month tag on the suppression system.
- Any permit and plans on file for the hood.
- A look at the duct cleanouts, to confirm the access panels exist and are not blocked.
Adding a fryer or relocating a line of equipment often means changes to the hood and suppression system as well. A pre-engineered suppression system is installed within the limits it was tested for, so the licensed company confirms the layout before anything moves. The building department says whether the change needs a fresh permit.
Licenses for this work
Chapter 489 licenses mechanical and sheet metal contractors in Florida. The building department can say which contractor license it accepts for a hood and grease duct, since that varies. Suppression work is separate and needs a State Fire Marshal license. Doing or advertising contracting without the proper license is a crime, and the DBPR license search shows any contractor's status.
A request for hood, duct or exhaust fan work goes through the form to the number of local companies you choose (one to five).
Questions
Is a Type I hood needed in every commercial kitchen?
Only over cooking that produces grease or smoke. Dishwashers and other heat or moisture equipment take a Type II hood, and the code lists a few exceptions such as low-grease electric appliances passing UL 710B.
What height does the fan discharge need above a roof?
The grease duct discharge sits at least 40 inches above the roof surface. The duct under an upblast fan rises at least 18 inches, and the building department confirms what it enforces.
Who checks a hood system before a restaurant opens?
The Mechanical Code calls for a performance test ahead of final approval, covering exhaust, makeup air and smoke capture. The building department can say who it accepts to run that test.
How can I look up a hood contractor's license?
The DBPR license search at myfloridalicense.com lists contractors. Suppression companies hold a separate State Fire Marshal license.